Difference between revisions of "ATM 33.50 (Exhaust Gas Temperature Model)"
From Nefmoto
MattDanger (Talk | contribs) |
|||
(5 intermediate revisions by one user not shown) | |||
Line 3: | Line 3: | ||
atm-main | atm-main | ||
− | atm-atm-b1 Exhaust gas temperature model (cylinder | + | atm-atm-b1 Exhaust gas temperature model (cylinder bank 1) overview |
− | bank 1) overview | + | |
atm-tmp-stat TMP_STAT engine speed & relative cylinder charge map and corrected for temperature for acceleration, intake air temp., catalyst heating, catalyst warming, ignition angle, lambda and cold engine | atm-tmp-stat TMP_STAT engine speed & relative cylinder charge map and corrected for temperature for acceleration, intake air temp., catalyst heating, catalyst warming, ignition angle, lambda and cold engine | ||
Line 37: | Line 36: | ||
atm-mst If tabst_w is not correct tabstatm = maximum value, request for delay B_nlatm as a function of engine speed and tatu-threshold) | atm-mst If tabst_w is not correct tabstatm = maximum value, request for delay B_nlatm as a function of engine speed and tatu-threshold) | ||
− | |||
− | |||
+ | <u>ATM 33.50 (Exhaust Gas Temperature Model) Function Description</u> | ||
− | The simulated exhaust gas | + | The simulated exhaust gas temperatures tabgm and tabgkrm (for SY_TURBO = 1) and catalytic converter |
− | temperatures tabgm and tabgkrm (for SY_TURBO = 1) and catalytic converter | + | |
temperatures tkatm and tikatm are used for the following purposes: | temperatures tkatm and tikatm are used for the following purposes: | ||
− | 1. Monitoring the catalyst. If the catalytic converter falls below its starting temperature, then | + | 1. Monitoring the catalyst. If the catalytic converter falls below its starting temperature, then a fault can be detected. |
− | a fault can be detected. | + | |
− | 2. For lambda control on the probe after the catalytic converter. This control is only activated after | + | 2. For lambda control on the probe after the catalytic converter. This control is only activated after engine start, when the catalyst has exceeded its start-up temperature. |
− | engine start, when the catalyst has exceeded its start-up temperature. | + | |
− | 3. For the probe heater control after engine start. If the simulated dew point is exceeded, the probe | + | 3. For the probe heater control after engine start. If the simulated dew point is exceeded, the probe heater is turned on. |
− | heater is turned on. | + | |
− | 4. Monitoring the heated exhaust gas oxygen (HEGO) sensor (i.e. lambda probe) heating system. If the | + | 4. Monitoring the heated exhaust gas oxygen (HEGO) sensor (i.e. lambda probe) heating system. If the exhaust gas temperature exceeds 800°C for example, then the lambda probe heater will be switched off, so that the probe is not too hot. |
− | exhaust gas temperature exceeds 800°C for example, then the lambda probe heater | + | |
− | will be switched off, so that the probe is not too hot. | + | |
5. For fan motor control. | 5. For fan motor control. | ||
Line 70: | Line 62: | ||
Steady-state temperature (tatmsta): the same applies for takrstc | Steady-state temperature (tatmsta): the same applies for takrstc | ||
− | With the engine speed/relative cylinder charge map KFTATM the steady-state exhaust | + | With the engine speed/relative cylinder charge map KFTATM the steady-state exhaust gas temperature before the catalyst is set. This temperature is corrected for ambient temperature or simulated ambient temperature from the characteristic ATMTANS: |
− | gas temperature before the catalyst is set. This temperature is corrected for | + | |
− | ambient temperature or simulated ambient temperature from the characteristic | + | |
− | ATMTANS: | + | |
during boost with the constant TATMSA, | during boost with the constant TATMSA, | ||
Line 99: | Line 88: | ||
Different temperature increases are applied for the temperature in the catalytic converter tikatm and the temperature after the catalytic converter tkatm due to exothermic reaction and cooling and different ignition angles and lambda-corrections. | Different temperature increases are applied for the temperature in the catalytic converter tikatm and the temperature after the catalytic converter tkatm due to exothermic reaction and cooling and different ignition angles and lambda-corrections. | ||
− | The time-based influence of the exhaust gas temperature before the catalytic | + | The time-based influence of the exhaust gas temperature before the catalytic converter: |
− | converter: | + | |
Line 115: | Line 103: | ||
− | The initial values ​​for the exhaust and catalyst temperature at engine start can be calculated from the temperatures at switch-off and delay times. The starting values ​​for the exhaust gas and catalyst temperatures should approximate to the manifold wall temperatures at the | + | The initial values ​​for the exhaust and catalyst temperature at engine start can be calculated from the temperatures at switch-off and delay times. The starting values ​​for the exhaust gas and catalyst temperatures should approximate to the manifold wall temperatures at the probe insertion points a few minutes after switch-off. |
− | probe insertion points a few minutes after switch-off. | + | |
The filter for the exhaust gas temperature is stopped by setting B_stend = 0. | The filter for the exhaust gas temperature is stopped by setting B_stend = 0. | ||
The filter for the manifold wall temperature is stopped when B_atmtpa = 1. The | The filter for the manifold wall temperature is stopped when B_atmtpa = 1. The | ||
Line 142: | Line 129: | ||
− | The dew point end time is approximately proportional to the heat quantity after engine start. The heat quantity = Integral (temp. | + | The dew point end time is approximately proportional to the heat quantity after engine start. The heat quantity = Integral (temp. x air mass x C<sub>p</sub>) is calculated from the steady-state exhaust gas temperature tatmsta plus TATMWMK multiplied by the air mass. The result of the integration multiplied by the heat capacity at constant pressure C<sub>p</sub> (approximately 1 kJ/kgK) gives the heat quantity. |
Line 238: | Line 225: | ||
- TATMSA | - TATMSA | ||
− | |||
Boost can cause low exhaust temperatures that fall below the starting temperature of the catalyst. The longer the time period for the thrust condition, the lower the exhaust and catalyst temperatures. For catalyst diagnosis during boost, the exhaust gas temperature model is more likely to calculate a lower value than the measured temperature. | Boost can cause low exhaust temperatures that fall below the starting temperature of the catalyst. The longer the time period for the thrust condition, the lower the exhaust and catalyst temperatures. For catalyst diagnosis during boost, the exhaust gas temperature model is more likely to calculate a lower value than the measured temperature. | ||
Line 244: | Line 230: | ||
- ATMTANS | - ATMTANS | ||
− | |||
At low ambient temperatures, exhaust gas temperature can fall below the catalyst start-up temperature. Therefore, the model temperature is only corrected at the low temperature range. | At low ambient temperatures, exhaust gas temperature can fall below the catalyst start-up temperature. Therefore, the model temperature is only corrected at the low temperature range. | ||
Line 250: | Line 235: | ||
- TATMKH | - TATMKH | ||
− | |||
As long as the catalyst-heating measures are effective, higher exhaust temperatures will result. | As long as the catalyst-heating measures are effective, higher exhaust temperatures will result. | ||
Line 256: | Line 240: | ||
- TATMKW | - TATMKW | ||
− | |||
The catalyst operating temperature will not be not reached during prolonged idling, so the exhaust gas temperature can be raised by the catalyst warming function. | The catalyst operating temperature will not be not reached during prolonged idling, so the exhaust gas temperature can be raised by the catalyst warming function. | ||
Line 262: | Line 245: | ||
- KFATMZW | - KFATMZW | ||
− | |||
The temperature increase as a result of ignition angle retardation can be determined on a rolling road dynamometer. First, on the dynamometer, the characteristic field values ​​KFTATM are applied without ignition angle correction. Ignition angles are then modified so that allowed etazwist values will result in the map. Through the corresponding air mass, the temperature increase will then be displayed in the map KFATMZW. | The temperature increase as a result of ignition angle retardation can be determined on a rolling road dynamometer. First, on the dynamometer, the characteristic field values ​​KFTATM are applied without ignition angle correction. Ignition angles are then modified so that allowed etazwist values will result in the map. Through the corresponding air mass, the temperature increase will then be displayed in the map KFATMZW. | ||
Line 268: | Line 250: | ||
- KFATMLA | - KFATMLA | ||
− | |||
The exhaust temperature is reduced by enrichment. The application is similar to KFATMZW, except that the ignition angle efficiency is changed instead of the enrichment factor. | The exhaust temperature is reduced by enrichment. The application is similar to KFATMZW, except that the ignition angle efficiency is changed instead of the enrichment factor. | ||
Line 274: | Line 255: | ||
- TATMTMOT | - TATMTMOT | ||
− | |||
− | The map KFTATM is applied with a warm engine. Thus, the model exhaust gas temperature has smaller deviations during cold start. For this operating mode, the temperature is corrected with the difference of the cold engine temperature and the warm engine temperature. | + | The map KFTATM is applied with a warm engine. Thus, the model exhaust gas temperature has smaller deviations during cold start. For this operating mode, the temperature is corrected with the difference of the cold engine temperature and the warm engine temperature. TATMTMOT should be about 90 to 100°C. |
− | + | ||
− | + | ||
− | TATMTMOT | + | |
− | should be about 90 to 100°C. | + | |
4. Maps ZATMAML, ZATMRML, FATMRML, ZATMKML, ZATMKKML, ZATMIKML und ZATMIKKML | 4. Maps ZATMAML, ZATMRML, FATMRML, ZATMKML, ZATMKKML, ZATMIKML und ZATMIKKML | ||
− | |||
− | The air-mass-dependent time constants ZATMAML, ZATMRML (temperature measuring points 1 or 3), and ZATMKML, ZATMKKML, ZATMIKML, ZATMIKKML (temperature measuring point 4), can help to more accurately | + | The air-mass-dependent time constants ZATMAML, ZATMRML (temperature measuring points 1 or 3), and ZATMKML, ZATMKKML, ZATMIKML, ZATMIKKML (temperature measuring point 4), can help to more accurately determine “spikes in the air mass” during sudden load variations. Thereby "air mass jumps" at full load and in particular during boost can be avoided. For example, for an air mass jump from 30 kg/hr to 80 kg/hr, the measured time constant is applied to the air mass flow of 80 kg/hr. For large air mass jumps during idle, the time constants ZATMKKML and ZATMIKKML can be input instead of ZATMKML or ZATMIKML if required. |
− | determine “spikes in the air mass” during sudden load variations. Thereby "air mass jumps" at full load and in particular during boost can be avoided. For example, for an air mass jump from 30 kg/hr to 80 kg/hr, the measured time constant is applied to the air mass flow of 80 kg/hr. For large | + | |
− | air mass jumps during idle, the time constants ZATMKKML and ZATMIKKML can be input instead of ZATMKML or ZATMIKML if required. | + | |
5. Block EXOTHERME: | 5. Block EXOTHERME: | ||
− | |||
- KATMEXML | - KATMEXML | ||
− | |||
The exothermic temperature is a function of air mass flow (warming by realizing emissions, reducing warming via a larger air mass). First KATMEXML applies, then KLATMZWE, KLATMLAE. | The exothermic temperature is a function of air mass flow (warming by realizing emissions, reducing warming via a larger air mass). First KATMEXML applies, then KLATMZWE, KLATMLAE. | ||
Line 301: | Line 272: | ||
- KLATMZWE | - KLATMZWE | ||
− | |||
When ignition angle retardation increases the temperature before the catalyst, the catalyst temperature drops. | When ignition angle retardation increases the temperature before the catalyst, the catalyst temperature drops. | ||
Line 307: | Line 277: | ||
- KLATMLAE | - KLATMLAE | ||
− | |||
− | For | + | For lambda < 1 (richer), the air mass is lacking to improve emissions so the catalyst temperature decreases. |
− | lambda < 1 (richer), the air mass is lacking to improve emissions so the | + | |
− | catalyst temperature decreases. | + | |
- TABGMEX | - TABGMEX | ||
− | |||
− | If | + | If the temperature before the catalyst tabgm < TABGMEX (catalyst switch-off temperature) then the temperature correction = TKATMOE. |
− | the temperature before the catalyst tabgm < TABGMEX (catalyst switch-off | + | |
− | temperature) then the temperature correction = TKATMOE. | + | |
- TKATMOE | - TKATMOE | ||
− | |||
− | Temperature | + | Temperature correction during boost or through tabgm> TABGMEX |
− | correction during boost or through tabgm> TABGMEX | + | |
- TATMSAE | - TATMSAE | ||
− | |||
− | Temperature | + | Temperature increase in the boost in the catalyst in terms of tkatm |
− | increase in the boost in the catalyst in terms of tkatm | + | |
Line 339: | Line 299: | ||
− | - | + | - KATMIEXML, KLATMIZWE, KLATMILAE, TIKATMOE |
− | KATMIEXML, KLATMIZWE, KLATMILAE, TIKATMOE | + | |
− | + | ||
− | Application | + | Application depends on the application for Block EXOTHERME |
− | depends on the application for Block EXOTHERME | + | |
- TATMSAE | - TATMSAE | ||
− | |||
− | Temperature | + | Temperature increase in the thrust in the catalyst in terms of tikatm |
− | increase in the thrust in the catalyst in terms of tikatm | + | |
− | 6. | + | 6. Dew point end times for exhaust gas temperatures vary greatly between the centre of the exhaust pipe and the pipe wall. Dew point end times for the tube wall temperatures before the catalyst (temperature measuring points 2) or after the catalyst (temperature measuring points 5) should be used. These times are usually due to delaying control readiness for too long, in which case the temperature gradients at the probe mounting location must be examined more closely. To avoid probe damage by “water hammer”, the sensor heater must be fully turned on until the dew point temperature is exceeded or the dew point end time is detected thus condensation will no longer occur. |
− | Dew point end times for exhaust gas temperatures vary greatly between the | + | |
− | centre of the exhaust pipe and the pipe wall. Dew point end times for the tube | + | |
− | wall temperatures before the catalyst (temperature measuring points 2) or after | + | |
− | the catalyst (temperature measuring points 5) should be used. These times are | + | |
− | usually due to delaying control readiness for too long, in which case the | + | |
− | temperature gradients at the probe mounting location must be examined more | + | |
− | closely. To avoid probe damage by “water hammer”, the sensor heater must be fully | + | |
− | turned on until the dew point temperature is exceeded or the dew point end time | + | |
− | is detected thus condensation will no longer occur. | + | |
− | When | + | When the switch-off time in the ECU delay is calculated, then the switch-off time tabst_w after ECU delay will be incorrect. At engine start after ECU delay, the switch-off time tabstatm therefore, will be set to the maximum value of 65,535 (i.e. 2<sup>16</sup>-1). The ECU delay requirement for the time TNLATM when engine speed > TNLATMTM & tumg (tatu) > TNLATMTU. |
− | the switch-off time in the ECU delay is calculated, then the switch-off time | + | |
− | tabst_w after ECU delay will be incorrect. At engine start after ECU delay, the | + | |
− | switch-off time tabstatm therefore, will be set to the maximum value of 65,535 | + | |
− | (i.e. 2<sup>16</sup>-1). The ECU delay | + | |
− | requirement for the time TNLATM when engine speed > TNLATMTM & tumg (tatu) | + | |
− | > TNLATMTU. | + | |
− | 8. | + | 8. For blocks KR_STAT and KR_DYN as appropriate, the descriptions in points 3 and |
− | For blocks KR_STAT and KR_DYN as appropriate, the descriptions in points 3 and | + | |
4 shall apply. | 4 shall apply. | ||
− | <u>Typical | + | <u>Typical Values:</u> |
− | Values:</u> | + | |
− | + | ||
− | KFTATM: | + | KFTATM: x: engine speed/RPM, y: relative cylinder charge/%, z: temperature/°C |
− | x: engine speed/RPM, y: relative cylinder charge/%, z: temperature/°C | + | |
− | + | ||
{| border="1" | {| border="1" | ||
Line 560: | Line 495: | ||
900 | 900 | ||
|} | |} | ||
+ | |||
+ | |||
KFATMZW: x: temperature/°C, y: ml_w/kg/hr, z: etazwimt | KFATMZW: x: temperature/°C, y: ml_w/kg/hr, z: etazwimt | ||
Line 667: | Line 604: | ||
| | | | ||
245 | 245 | ||
− | |} | + | |} |
− | + | ||
− | + | ||
+ | KFATMLA: x: temperature/°C, y: ml_w/kg/hr, z: lamsbg_w | ||
{| border="1" | {| border="1" | ||
Line 777: | Line 714: | ||
| | | | ||
120 | 120 | ||
− | |} | + | |} |
− | + | ||
− | + | ||
+ | KFWMABG: x: energy/kJ, y: tabgmst/°C, z: tmst/°C | ||
{| border="1" | {| border="1" | ||
Line 886: | Line 823: | ||
|} | |} | ||
− | KFWMKAT values ​​correspond to KFWMABG | + | |
+ | KFWMKAT values ​​correspond to KFWMABG x 5 | ||
In the heat quantity maps KFWMABG and KFWMKAT a value of 0.0 is never required! It should always have at least the value to be entered; the 2 sec corresponds to idle after cold start. Only then does the repeat-start counter operate after several starts where the dew point was not reached. | In the heat quantity maps KFWMABG and KFWMKAT a value of 0.0 is never required! It should always have at least the value to be entered; the 2 sec corresponds to idle after cold start. Only then does the repeat-start counter operate after several starts where the dew point was not reached. | ||
Line 892: | Line 830: | ||
ZATMAML | ZATMAML | ||
+ | |||
ml_w/kg/hr, Time constant/sec 10, 30 ; 20, 20 ; 40, 13 ; 80, 5 ; 180, 4 ; 400, 3 ; 600, 2 ; | ml_w/kg/hr, Time constant/sec 10, 30 ; 20, 20 ; 40, 13 ; 80, 5 ; 180, 4 ; 400, 3 ; 600, 2 ; | ||
ZATMKML | ZATMKML | ||
+ | |||
ml_w/kg/hr, Time constant/sec 10, 150 ; 20, 60 ; 40, 35 ; 80, 20 ; 180, 10 ; | ml_w/kg/hr, Time constant/sec 10, 150 ; 20, 60 ; 40, 35 ; 80, 20 ; 180, 10 ; | ||
400, 7 ; 600, 4 ; | 400, 7 ; 600, 4 ; | ||
ZATMIKML | ZATMIKML | ||
− | value represents approximately ZATMKML | + | |
+ | value represents approximately ZATMKML x 0.3 | ||
ZATMKKML | ZATMKKML | ||
+ | |||
for neutral input, the data must correlate to ZATMKML | for neutral input, the data must correlate to ZATMKML | ||
ZATMIKKML | ZATMIKKML | ||
+ | |||
for neutral input, the data must correlate to ZATMIKML | for neutral input, the data must correlate to ZATMIKML | ||
ZATMRML | ZATMRML | ||
− | ml_w/kg/hr, Time constant/sec 10, 300 ; 20, 80 ; 40, 55 ; 80, 30 ; 180, 20 ; | + | |
− | 400, 10 ; 600, 7 ; | + | ml_w/kg/hr, Time constant/sec 10, 300 ; 20, 80 ; 40, 55 ; 80, 30 ; 180, 20 ; 400, 10 ; 600, 7 ; |
FATMRML | FATMRML | ||
− | ml_w/kg/hr, Time constant/sec 10, 0.5 ; 20, 0.6 ; 40, 0.7 ; 80, 0.8 ; 180, 0.95; 400,0.95 ; 600, 0.96; | + | |
+ | ml_w/kg/hr, Time constant/sec 10, 0.5 ; 20, 0.6 ; 40, 0.7 ; 80, 0.8 ; 180, 0.95 ; 400,0.95 ; 600, 0.96; | ||
KATMEXML | KATMEXML | ||
+ | |||
ml_w/kg/hr, Time constant/sec 10, 0 ; 20, 0 ; 40, 0 ; 80, 0 ; 180, 0 ; 400, 0 ; | ml_w/kg/hr, Time constant/sec 10, 0 ; 20, 0 ; 40, 0 ; 80, 0 ; 180, 0 ; 400, 0 ; | ||
KLATMZWE | KLATMZWE | ||
+ | |||
etazwimt, Factor 1, 0 ; 0.95, 0 ; 0.9, 0 ; 0.8, 0 ; 0.7, 0 ; 0.6, 0 ; | etazwimt, Factor 1, 0 ; 0.95, 0 ; 0.9, 0 ; 0.8, 0 ; 0.7, 0 ; 0.6, 0 ; | ||
KLATMLAE | KLATMLAE | ||
+ | |||
lamsbg_w, Factor 1.15, 0 ; 1 , 0 ;0.95, 0 ; 0.9, 0 ; 0.8, 0 ; 0.7, 0 ; | lamsbg_w, Factor 1.15, 0 ; 1 , 0 ;0.95, 0 ; 0.9, 0 ; 0.8, 0 ; 0.7, 0 ; | ||
Line 930: | Line 877: | ||
KATMIEXML | KATMIEXML | ||
+ | |||
ml_w/kg/hr, Time constant/sec 10, 0 ; 20, 0 ; 40, 0 ; 80, 0 ; 180, 0 ; 400, 0 ; | ml_w/kg/hr, Time constant/sec 10, 0 ; 20, 0 ; 40, 0 ; 80, 0 ; 180, 0 ; 400, 0 ; | ||
− | KLATMIZWE | + | KLATMIZWE |
− | KLATMILAE lamsbg_w, Factor 1.15, 0 ; 1 , 0 ;0.95, 0 ; 0.9, 0 ; 0.8, 0 ; 0.7, 0 ; | + | etazwimt, Factor 1, 0 ; 0.95, 0 ; 0.9, 0; 0.8, 0 ; 0.7, 0 ; 0.6, 0 ; |
+ | |||
+ | KLATMILAE | ||
+ | |||
+ | lamsbg_w, Factor 1.15, 0 ; 1 , 0 ;0.95, 0 ; 0.9, 0 ; 0.8, 0 ; 0.7, 0 ; | ||
TIKATMOE: 0°C | TIKATMOE: 0°C | ||
Line 940: | Line 892: | ||
KFATMABKA: x: tatu/°C, y: tabstatm_w/seconds, z: no units | KFATMABKA: x: tatu/°C, y: tabstatm_w/seconds, z: no units | ||
− | |||
{| border="1" | {| border="1" | ||
Line 1,033: | Line 984: | ||
0.00 | 0.00 | ||
|} | |} | ||
− | |||
− | |||
+ | |||
+ | KFATMABKK: x: tatu/°C, y: tabstatm_w [s], z: no units | ||
{| border="1" | {| border="1" | ||
Line 1,131: | Line 1,082: | ||
ATMTANS tatu/°C, Temp./°C -40, 60 ; -10, 20 ; 20, 0 ; | ATMTANS tatu/°C, Temp./°C -40, 60 ; -10, 20 ; 20, 0 ; | ||
− | |||
TATMSA: 100°C | TATMSA: 100°C | ||
− | |||
TATMKH: 80°C | TATMKH: 80°C | ||
− | |||
TATMTRKH: 200°C | TATMTRKH: 200°C | ||
− | |||
TATMKW: 100°C | TATMKW: 100°C | ||
− | |||
TATMTMOT: 90°C | TATMTMOT: 90°C | ||
− | |||
TATMSTI: 20°C | TATMSTI: 20°C | ||
− | |||
TASTBFA: 40°C | TASTBFA: 40°C | ||
− | |||
− | TKSTBFA: | + | TKSTBFA: 40°C |
− | 40°C | + | |
− | + | ||
− | TATMWMK: | + | TATMWMK: -80°C |
− | -80°C | + | |
− | + | ||
− | WMABGKH: | + | WMABGKH: Factor of 1.0 |
− | Factor of 1.0 | + | |
− | + | ||
− | WMKATKH | + | WMKATKH: Factor of 1.0 |
− | Factor of 1.0 | + | |
− | + | ||
− | FWMABGW | + | FWMABGW: Factor of 0.25 |
− | Factor of 0.25 | + | |
− | + | ||
− | FWMKATW | + | FWMKATW: Factor of 0.25 |
− | Factor of 0.25 | + | |
− | + | ||
− | DTUMTAT: | + | DTUMTAT: 20°C |
− | 20°C | + | |
− | + | ||
VTUMTAT: 40 km/h | VTUMTAT: 40 km/h | ||
− | |||
NTUMTAT: 1800 rpm | NTUMTAT: 1800 rpm | ||
− | |||
IMTUMTAT: 1 kg | IMTUMTAT: 1 kg | ||
− | |||
TUMTAIT: 20°C | TUMTAIT: 20°C | ||
− | |||
TNLATMTM: 80°C | TNLATMTM: 80°C | ||
− | |||
TNLATMTU: 5°C | TNLATMTU: 5°C | ||
− | |||
TNLATM: 660 seconds | TNLATM: 660 seconds | ||
− | |||
Only when SY_TURBO = 1: | Only when SY_TURBO = 1: | ||
− | |||
− | For | + | For neutral input (tabgkrm_w = tabgm_w) |
− | neutral input (tabgkrm_w = tabgm_w) | + | |
− | + | ||
KFATMKR = KFTATM | KFATMKR = KFTATM | ||
− | |||
KFATZWK = KFATMZW | KFATZWK = KFATMZW | ||
− | |||
KFATLAK = KFATMLA | KFATLAK = KFATMLA | ||
− | |||
TATMKRSA = TATMSA | TATMKRSA = TATMSA | ||
− | |||
ZATRKRML = ZATMRML | ZATRKRML = ZATMRML | ||
− | |||
ZATAKRML = ZATMAML | ZATAKRML = ZATMAML | ||
− | |||
− | FATRKRML | + | FATRKRML = FATMRML |
− | = FATMRML | + | |
− | + | ||
ATMTANS | ATMTANS | ||
Line 1,236: | Line 1,147: | ||
− | The | + | The functional data for cylinder bank 2 correspond to the functional data from cylinder bank 1 Note: |
− | functional data for cylinder bank 2 correspond to the functional data from cylinder | + | |
− | bank 1 Note: | + | |
− | In | + | In order that ATM 22:20 for the application is backward compatible the default values should be entered thus: ​​KATMEXML, KLATMZWE, KLATMLAE, TKATMOE = 0 and TABGMEX = 1220°C. |
− | order that ATM 22:20 for the application is backward compatible the default | + | |
− | values should be entered thus: ​​KATMEXML, KLATMZWE, KLATMLAE, TKATMOE = 0 and TABGMEX = 1220°C. | + | |
− | In | + | In order that ATM 33.10 remains application-neutral with ATM 22.50, TATMTRKH must be set equal to TATMKH and WMKATKH should be set equal to 1. Tikatm is not used in a function because the input can be used in the path in the exhaust gas temperature model without impact on safety, however, the default values for ​​KATMIEXML, KLATMIZWE, KLATMILAE and TIKATMOE should be set equal to 0 and TABGMEX = 1220°C. |
− | order that ATM 33.10 remains application-neutral with ATM 22.50, TATMTRKH must | + | |
− | be set equal to TATMKH and WMKATKH should be set equal to 1. Tikatm is not used | + | |
− | in a function because the input can be used in the path in the exhaust gas | + | |
− | temperature model without impact on safety, however, the default values for ​​KATMIEXML, | + | |
− | KLATMIZWE, KLATMILAE and TIKATMOE should be set equal to 0 and TABGMEX = 1220°C. | + | |
In DKATSP areas TMINKATS and TMAXKATS, a high accuracy is required for tikatm! | In DKATSP areas TMINKATS and TMAXKATS, a high accuracy is required for tikatm! | ||
+ | |||
+ | |||
+ | <u>Abbreviations</u> | ||
{| border="1" | {| border="1" |
Latest revision as of 10:15, 8 January 2012
Refer to the funktionsrahmen for the following diagrams:
atm-main
atm-atm-b1 Exhaust gas temperature model (cylinder bank 1) overview
atm-tmp-stat TMP_STAT engine speed & relative cylinder charge map and corrected for temperature for acceleration, intake air temp., catalyst heating, catalyst warming, ignition angle, lambda and cold engine
atm-dynamik Temperature dynamic for exhaust gas and catalytic converter temperature (in and near the catalytic converter)
atm-tabgm Temperature dynamic: exhaust gas, exhaust pipe wall effect, from the exhaust gas temperature tabgm
atm-tkatm Temperature dynamic for the temperature near the catalytic converter
atm-exotherme Exothermic temperature increase near the catalyst from measurement sites tabgm to tikatm
atm-tikatm Temperature dynamic for the temperature in the catalytic converter
atm-exoikat Exothermic temperature increase in the catalyst from measurement sites tabgm to tikatm
atm-kr-stat Exhaust gas temperature in the exhaust manifold under steady-state conditions
atm-kr-dyn Exhaust gas temperature in the exhaust manifold under dynamic conditions
atm-tmp-start Calculation of the exhaust gas or exhaust pipe wall temperature at engine start
atm-tpe-logik Calculation of the dew point at the pre-cat and post-cat lambda probes
atm-sp-nachl Storage of the dew point conditions at engine switch off
atm-mean Calculation of etazwist average values
atm-tmp-umgm If no ambient temperature sensor is available, calculate a substitute from ambient temperature (tans)
atm-mst If tabst_w is not correct tabstatm = maximum value, request for delay B_nlatm as a function of engine speed and tatu-threshold)
ATM 33.50 (Exhaust Gas Temperature Model) Function Description
The simulated exhaust gas temperatures tabgm and tabgkrm (for SY_TURBO = 1) and catalytic converter temperatures tkatm and tikatm are used for the following purposes:
1. Monitoring the catalyst. If the catalytic converter falls below its starting temperature, then a fault can be detected.
2. For lambda control on the probe after the catalytic converter. This control is only activated after engine start, when the catalyst has exceeded its start-up temperature.
3. For the probe heater control after engine start. If the simulated dew point is exceeded, the probe heater is turned on.
4. Monitoring the heated exhaust gas oxygen (HEGO) sensor (i.e. lambda probe) heating system. If the exhaust gas temperature exceeds 800°C for example, then the lambda probe heater will be switched off, so that the probe is not too hot.
5. For fan motor control.
6. For switching on component protection.
This function provides only a rough approximation of the exhaust gas and catalytic converter temperature profiles, whereas throughout the application especially the four monitoring areas (dew point profiles in the exhaust gas, catalytic converter monitoring, enabling and shutting off lambda probe heating and high temperatures for component protection) should be considered to be critical.
1. Basic function
Steady-state temperature (tatmsta): the same applies for takrstc
With the engine speed/relative cylinder charge map KFTATM the steady-state exhaust gas temperature before the catalyst is set. This temperature is corrected for ambient temperature or simulated ambient temperature from the characteristic ATMTANS:
during boost with the constant TATMSA,
during catalyst heating with the constant TATMKH; catalyst warming with the constant TATMKW
with the ignition-angle efficiency map KFATMZW temperature as a function of ML and ETAZWIST
with the desired lambda map KFATMLA temperature as a function of ML and LAMSBG_W
for a cold engine block (TMOT - TATMTMOT) with TATMTMOT = 90°C.
The catalyst temperature (exothermic) is corrected for:
Temperature increase with the characteristic KATMEXML or KATMIEXML as a function of air mass
Temperature reduction with KLATMZWE or KLATMIZWE as a function of etazwimt (ignition angle influence)
Lambda influence with KLATMLAE or KLATMILAE as a function of lambsbg_w
Temperature set at TKATMOE or TIKATMOE at tabgm <TABGMEX or B_sa = 1
Different temperature increases are applied for the temperature in the catalytic converter tikatm and the temperature after the catalytic converter tkatm due to exothermic reaction and cooling and different ignition angles and lambda-corrections.
The time-based influence of the exhaust gas temperature before the catalytic converter:
Using a PT1 filter (filter time constant ZATMAML) the dynamics of the exhaust gas temperature are simulated and with a PT1 filter (time constant ZATMRML) the dynamics of the inlet manifold wall temperature are simulated.
The exhaust gas temperature and inlet manifold wall temperature are weighted by the division factor FATMRML.
The catalytic converter temperature tkatm is calculated from the exhaust gas temperature tabgm along with the PT1 filter (filter time constant ZATMKML).
The temperature in the catalyst tikatm is modelled from the exhaust gas temperature tabgm via three filters (time constant ZATMIKML) using the heat transfer principle. Due to a thrust caused by the small air mass flow in the catalytic converter, there is a possible exhaust gas temperature increase due to the greater influence on the matrix temperature by the exhaust gas throughput. This thrust-based temperature increase can be modelled by the positive B_sa side with a temperature, which is composed of the catalyst temperature tikatm and an offset TATMSAE, will be initialised. The time constants of the PT1-filter ZATMIKML are represented by air-mass-dependent characteristic curves.
The initial values for the exhaust and catalyst temperature at engine start can be calculated from the temperatures at switch-off and delay times. The starting values for the exhaust gas and catalyst temperatures should approximate to the manifold wall temperatures at the probe insertion points a few minutes after switch-off.
The filter for the exhaust gas temperature is stopped by setting B_stend = 0.
The filter for the manifold wall temperature is stopped when B_atmtpa = 1. The
filter for the catalyst temperature will be enabled only when B_atmtpk = 1.
2. Dew Point Detection
Initial values for the exhaust gas temperature tabgmst and catalyst temperature tkatmst
When stopping the engine (C_nachl 0 ® 1) the temperatures tabgm and tkatm are stored.
When starting the engine, the initial temperatures tabgmst and tkatmst are calculated from the switch-off temperature (corrected for ambient temperature) and a factor obtained from maps KFATMABKA or KFATMABKK as a function of tabstatm and tatu.
During power fail the switch-off temperature will be determined from the constant TATMSTI.
For test condition (B_faatm = 1), the initial temperatures are given by the constants TASTBFA and TKSTBFA.
Integrated Heat Quantity iwmatm_w
The dew point end time is approximately proportional to the heat quantity after engine start. The heat quantity = Integral (temp. x air mass x Cp) is calculated from the steady-state exhaust gas temperature tatmsta plus TATMWMK multiplied by the air mass. The result of the integration multiplied by the heat capacity at constant pressure Cp (approximately 1 kJ/kgK) gives the heat quantity.
Dew point end for the pre-cat lambda probe B_atmtpa and post-cat lambda probe B_atmtpk
The calculated exhaust gas temperature at engine start tabgmst approximates to the exhaust pipe wall temperature. If the exhaust pipe wall temperature is greater than 60°C for example then no condensation occurs.
The values in the map KFWMABG for these temperatures are less than 14 kJ, so the dew point end is detected immediately, or after only a few seconds.
For catalytic converter heating with thermal reaction (B_trkh = 1) the values in maps KFWMABG or KFWMKAT are multiplied by the factor WMKATKH or WMABGKH respectively. Thus, the dew point end-times are very short for this mode of operation.
Repeated starts (extension of the dew point-end-times)
If the engine had not reached the dew point end (B_atmtpa = 0 and B_atmtpf = 0) then when the engine restarts, the counter zwmatmf is increased by 1. After several periods of very short engine running (e.g. 3), the counter zwmatmf value would be set equal to 3. With a constant FWMABGW = 0.25 for example, the values in the map KFWMABG increase by a factor equal to (zwmatmf x KFWMABG + 1) = 1.75. When the engine starts, the dew point end time from the last engine run is detected and the
counter zwmatmf is reset.
Storage of the dew point end condition in the delay
For the determination of repeat start dew point end the conditions B_atmtpa in the flag B_atmtpf and B_atmtpk in the flag B_atmtpl are saved at engine switch-off due to a regular switch-off using the ignition or stall (B_stndnl). The function of dew point end for the post-cat lambda probe B_atmtpk
is analogous to the function for B_atmtpa.
3. Calculation of a simulated ambient temperature from the intake air temperature (tans) if no ambient temperature sensor is available.
The simulated temperature tatu will be used for calculating the temperature correction via the characteristic ATMTANS and for determining the starting temperatures tabgmst and tkatmst. The intake air temperature (tans) is corrected with the constant DTUMTAT and under certain conditions stored in continuous RAM. If for example at engine start, the temperature tatu > tans, then the temperature value tatu is set on the lower tans value.
With the constant TATMWMK (negative value) the difference in dew point end between catalyst heating and no catalyst heating can be increased.
When catalytic converter heating is active B_khtr = 1 and the bit B_atmtpa can be set equal to 1 immediately after engine start. This is possible only when no problematic condensation is formed during catalyst heating.
With the system constants SY_STERVK = 1 cylinder bank 2 can be applied separately for stereo systems.
For SY_TURBO = 1 the exhaust gas temperature tabgm is essentially identical in addition to the modeled temperature in the manifold tabgkrm.
ATM 33.50 Application Notes
1. Installation locations for temperature sensors in this application, running in
the direction of flow:
- In probe installation position before catalytic converter-
1. Exhaust gas temperature (pipe centre) for the high temperatures at high loads for probe heater switch off
2. Manifold wall temperature for the determination of the dew-end times. (Condensation protection)
- Before the catalytic converter
3. Exhaust gas temperature (pipe centre) for the catalyst start-up temperature
- In the catalytic converter
4. Ceramic temperature in and after catalytic converter (in the last third of the catalytic converter or behind the adjoining matrix) to determine the air-mass-dependent time constants.
- After the catalytic converter
5. Pipe wall temperature at probe installation site for the determination of the dew-end times (condensation protection).
Temperature measuring point 3 can be omitted if the distance from probe to catalytic converter is smaller than about 30 cm. The temperature drop from probe installation site to catalytic converter can then be neglected.
For the application of the functional data the modelled temperatures will always be compared with the measured temperatures and the functional data amended until a sufficiently high accuracy is achieved. In so doing, it will be the actual catalyst temperature, the temperature increase due to the exothermic reaction is not considered in the model.
2. Map KFTATM
For the determination of the steady-state temperature for example, before the catalytic converter the temperature corrections should not function. The cooling capacity of the wind on the dynamometer or on the measuring wheel can be simulated only very roughly at the higher engine load range. The map values can be determined on the rolling road dynamometer, but should be corrected on an
appropriate test drive.
3. Temperature Corrections
- TATMSA
Boost can cause low exhaust temperatures that fall below the starting temperature of the catalyst. The longer the time period for the thrust condition, the lower the exhaust and catalyst temperatures. For catalyst diagnosis during boost, the exhaust gas temperature model is more likely to calculate a lower value than the measured temperature.
- ATMTANS
At low ambient temperatures, exhaust gas temperature can fall below the catalyst start-up temperature. Therefore, the model temperature is only corrected at the low temperature range.
- TATMKH
As long as the catalyst-heating measures are effective, higher exhaust temperatures will result.
- TATMKW
The catalyst operating temperature will not be not reached during prolonged idling, so the exhaust gas temperature can be raised by the catalyst warming function.
- KFATMZW
The temperature increase as a result of ignition angle retardation can be determined on a rolling road dynamometer. First, on the dynamometer, the characteristic field values KFTATM are applied without ignition angle correction. Ignition angles are then modified so that allowed etazwist values will result in the map. Through the corresponding air mass, the temperature increase will then be displayed in the map KFATMZW.
- KFATMLA
The exhaust temperature is reduced by enrichment. The application is similar to KFATMZW, except that the ignition angle efficiency is changed instead of the enrichment factor.
- TATMTMOT
The map KFTATM is applied with a warm engine. Thus, the model exhaust gas temperature has smaller deviations during cold start. For this operating mode, the temperature is corrected with the difference of the cold engine temperature and the warm engine temperature. TATMTMOT should be about 90 to 100°C.
4. Maps ZATMAML, ZATMRML, FATMRML, ZATMKML, ZATMKKML, ZATMIKML und ZATMIKKML
The air-mass-dependent time constants ZATMAML, ZATMRML (temperature measuring points 1 or 3), and ZATMKML, ZATMKKML, ZATMIKML, ZATMIKKML (temperature measuring point 4), can help to more accurately determine “spikes in the air mass” during sudden load variations. Thereby "air mass jumps" at full load and in particular during boost can be avoided. For example, for an air mass jump from 30 kg/hr to 80 kg/hr, the measured time constant is applied to the air mass flow of 80 kg/hr. For large air mass jumps during idle, the time constants ZATMKKML and ZATMIKKML can be input instead of ZATMKML or ZATMIKML if required.
5. Block EXOTHERME:
- KATMEXML
The exothermic temperature is a function of air mass flow (warming by realizing emissions, reducing warming via a larger air mass). First KATMEXML applies, then KLATMZWE, KLATMLAE.
- KLATMZWE
When ignition angle retardation increases the temperature before the catalyst, the catalyst temperature drops.
- KLATMLAE
For lambda < 1 (richer), the air mass is lacking to improve emissions so the catalyst temperature decreases.
- TABGMEX
If the temperature before the catalyst tabgm < TABGMEX (catalyst switch-off temperature) then the temperature correction = TKATMOE.
- TKATMOE
Temperature correction during boost or through tabgm> TABGMEX
- TATMSAE
Temperature increase in the boost in the catalyst in terms of tkatm
Block EXOIKAT:
- KATMIEXML, KLATMIZWE, KLATMILAE, TIKATMOE
Application depends on the application for Block EXOTHERME
- TATMSAE
Temperature increase in the thrust in the catalyst in terms of tikatm
6. Dew point end times for exhaust gas temperatures vary greatly between the centre of the exhaust pipe and the pipe wall. Dew point end times for the tube wall temperatures before the catalyst (temperature measuring points 2) or after the catalyst (temperature measuring points 5) should be used. These times are usually due to delaying control readiness for too long, in which case the temperature gradients at the probe mounting location must be examined more closely. To avoid probe damage by “water hammer”, the sensor heater must be fully turned on until the dew point temperature is exceeded or the dew point end time is detected thus condensation will no longer occur.
When the switch-off time in the ECU delay is calculated, then the switch-off time tabst_w after ECU delay will be incorrect. At engine start after ECU delay, the switch-off time tabstatm therefore, will be set to the maximum value of 65,535 (i.e. 216-1). The ECU delay requirement for the time TNLATM when engine speed > TNLATMTM & tumg (tatu) > TNLATMTU.
8. For blocks KR_STAT and KR_DYN as appropriate, the descriptions in points 3 and
4 shall apply.
Typical Values:
KFTATM: x: engine speed/RPM, y: relative cylinder charge/%, z: temperature/°C
800 |
1200 |
1800 |
2400 |
3000 |
4000 |
5000 |
6000 | |
15 |
380 |
400 |
420 |
450 |
480 |
520 |
550 |
580 |
22 |
400 |
420 |
450 |
480 |
520 |
550 |
580 |
610 |
30 |
420 |
450 |
480 |
520 |
550 |
580 |
610 |
650 |
50 |
450 |
480 |
520 |
550 |
580 |
610 |
650 |
700 |
70 |
470 |
520 |
550 |
580 |
610 |
660 |
700 |
750 |
100 |
490 |
550 |
580 |
610 |
650 |
700 |
750 |
790 |
120 |
510 |
560 |
610 |
650 |
700 |
750 |
790 |
840 |
140 |
530 |
580 |
650 |
700 |
750 |
790 |
840 |
900 |
KFATMZW: x: temperature/°C, y: ml_w/kg/hr, z: etazwimt
20 |
40 |
80 |
150 |
250 |
400 | |
1.00 |
0.0 |
0.0 |
0.0 |
0.0 |
0.0 |
0.0 |
0.95 |
15 |
40 |
50 |
60 |
70 |
75 |
0.90 |
15 |
60 |
80 |
100 |
125 |
140 |
0.80 |
20 |
80 |
120 |
150 |
180 |
200 |
0.70 |
25 |
100 |
150 |
190 |
210 |
220 |
0.60 |
30 |
115 |
175 |
210 |
230 |
245 |
KFATMLA: x: temperature/°C, y: ml_w/kg/hr, z: lamsbg_w
20 |
40 |
80 |
150 |
250 |
400 | |
1.15 |
5 |
10 |
30 |
50 |
60 |
70 |
1.00 |
0.0 |
0.0 |
0.0 |
0.0 |
0.0 |
0.0 |
0.95 |
5 |
10 |
20 |
30 |
40 |
45 |
0.90 |
15 |
25 |
40 |
50 |
60 |
75 |
0.80 |
30 |
40 |
60 |
70 |
85 |
100 |
0.70 |
40 |
60 |
80 |
90 |
100 |
120 |
KFWMABG: x: energy/kJ, y: tabgmst/°C, z: tmst/°C
-40 |
0 |
15 |
25 |
30 |
55 |
60 | |
-40 |
200 |
160 |
150 |
140 |
100 |
60 |
30 |
0 |
180 |
150 |
120 |
110 |
80 |
50 |
20 |
15 |
160 |
140 |
60 |
55 |
30 |
40 |
0.45 |
25 |
140 |
120 |
30 |
30 |
15 |
10 |
0.45 |
60 |
120 |
30 |
20 |
15 |
10 |
5 |
0.45 |
KFWMKAT values correspond to KFWMABG x 5
In the heat quantity maps KFWMABG and KFWMKAT a value of 0.0 is never required! It should always have at least the value to be entered; the 2 sec corresponds to idle after cold start. Only then does the repeat-start counter operate after several starts where the dew point was not reached.
ZATMAML
ml_w/kg/hr, Time constant/sec 10, 30 ; 20, 20 ; 40, 13 ; 80, 5 ; 180, 4 ; 400, 3 ; 600, 2 ;
ZATMKML
ml_w/kg/hr, Time constant/sec 10, 150 ; 20, 60 ; 40, 35 ; 80, 20 ; 180, 10 ; 400, 7 ; 600, 4 ;
ZATMIKML
value represents approximately ZATMKML x 0.3
ZATMKKML
for neutral input, the data must correlate to ZATMKML
ZATMIKKML
for neutral input, the data must correlate to ZATMIKML
ZATMRML
ml_w/kg/hr, Time constant/sec 10, 300 ; 20, 80 ; 40, 55 ; 80, 30 ; 180, 20 ; 400, 10 ; 600, 7 ;
FATMRML
ml_w/kg/hr, Time constant/sec 10, 0.5 ; 20, 0.6 ; 40, 0.7 ; 80, 0.8 ; 180, 0.95 ; 400,0.95 ; 600, 0.96;
KATMEXML
ml_w/kg/hr, Time constant/sec 10, 0 ; 20, 0 ; 40, 0 ; 80, 0 ; 180, 0 ; 400, 0 ;
KLATMZWE
etazwimt, Factor 1, 0 ; 0.95, 0 ; 0.9, 0 ; 0.8, 0 ; 0.7, 0 ; 0.6, 0 ;
KLATMLAE
lamsbg_w, Factor 1.15, 0 ; 1 , 0 ;0.95, 0 ; 0.9, 0 ; 0.8, 0 ; 0.7, 0 ;
TATMTP: 52°C
TKATMOE: 0°C
TATMSAE: 0°C
KATMIEXML
ml_w/kg/hr, Time constant/sec 10, 0 ; 20, 0 ; 40, 0 ; 80, 0 ; 180, 0 ; 400, 0 ;
KLATMIZWE
etazwimt, Factor 1, 0 ; 0.95, 0 ; 0.9, 0; 0.8, 0 ; 0.7, 0 ; 0.6, 0 ;
KLATMILAE
lamsbg_w, Factor 1.15, 0 ; 1 , 0 ;0.95, 0 ; 0.9, 0 ; 0.8, 0 ; 0.7, 0 ;
TIKATMOE: 0°C
KFATMABKA: x: tatu/°C, y: tabstatm_w/seconds, z: no units
10 |
50 |
180 |
360 |
600 |
1000 | |
-40 |
0.95 |
0.70 |
0.50 |
0.30 |
0.15 |
0.00 |
-15 |
0.95 |
0.70 |
0.50 |
0.30 |
0.15 |
0.00 |
0 |
0.95 |
0.70 |
0.50 |
0.30 |
0.15 |
0.00 |
15 |
0.95 |
0.70 |
0.50 |
0.30 |
0.15 |
0.00 |
40 |
0.95 |
0.70 |
0.50 |
0.30 |
0.15 |
0.00 |
KFATMABKK: x: tatu/°C, y: tabstatm_w [s], z: no units
10 |
50 |
180 |
360 |
600 |
1000 | |
-40 |
0.90 |
0.60 |
0.40 |
0.25 |
0.15 |
0.00 |
-15 |
0.90 |
0.60 |
0.40 |
0.25 |
0.15 |
0.00 |
0 |
0.90 |
0.60 |
0.40 |
0.25 |
0.15 |
0.00 |
15 |
0.90 |
0.60 |
0.40 |
0.25 |
0.15 |
0.00 |
40 |
0.90 |
0.60 |
0.40 |
0.25 |
0.15 |
0.00 |
ATMTANS tatu/°C, Temp./°C -40, 60 ; -10, 20 ; 20, 0 ;
TATMSA: 100°C
TATMKH: 80°C
TATMTRKH: 200°C
TATMKW: 100°C
TATMTMOT: 90°C
TATMSTI: 20°C
TASTBFA: 40°C
TKSTBFA: 40°C
TATMWMK: -80°C
WMABGKH: Factor of 1.0
WMKATKH: Factor of 1.0
FWMABGW: Factor of 0.25
FWMKATW: Factor of 0.25
DTUMTAT: 20°C
VTUMTAT: 40 km/h
NTUMTAT: 1800 rpm
IMTUMTAT: 1 kg
TUMTAIT: 20°C
TNLATMTM: 80°C
TNLATMTU: 5°C
TNLATM: 660 seconds
Only when SY_TURBO = 1:
For neutral input (tabgkrm_w = tabgm_w)
KFATMKR = KFTATM
KFATZWK = KFATMZW
KFATLAK = KFATMLA
TATMKRSA = TATMSA
ZATRKRML = ZATMRML
ZATAKRML = ZATMAML
FATRKRML = FATMRML
ATMTANS tans/°C, Temp./°C -40, 40 ; -20, 25 ; 0, 12 ; 20, 0 ; 60, -30
The functional data for cylinder bank 2 correspond to the functional data from cylinder bank 1 Note:
In order that ATM 22:20 for the application is backward compatible the default values should be entered thus: KATMEXML, KLATMZWE, KLATMLAE, TKATMOE = 0 and TABGMEX = 1220°C.
In order that ATM 33.10 remains application-neutral with ATM 22.50, TATMTRKH must be set equal to TATMKH and WMKATKH should be set equal to 1. Tikatm is not used in a function because the input can be used in the path in the exhaust gas temperature model without impact on safety, however, the default values for KATMIEXML, KLATMIZWE, KLATMILAE and TIKATMOE should be set equal to 0 and TABGMEX = 1220°C.
In DKATSP areas TMINKATS and TMAXKATS, a high accuracy is required for tikatm!
Abbreviations
Parameter |
Description |
ATMTAKR |
Correction for the manifold temperature |
ATMTANS |
Temperature correction for the exhaust gas temperature model |
DTUMTAT |
Offset: intake air temperature ® ambient temperature |
FATMRML |
Factor for the difference between exhaust gas & exhaust pipe wall temperature |
FATMRML2 |
Factor for the difference between exhaust gas & exhaust pipe wall temperature, cylinder bank 2 |
FATRKRML |
Factor for the difference between exhaust gas & wall temperature in the manifold |
FATRKRML2 |
Factor for the difference between exhaust gas & wall temperature in the manifold, cylinder bank 2 |
FWMABGW |
Factor for heat quantity during repeated starts for pre-cat exhaust gas dew points |
FWMABGW2 |
Factor for heat quantity during repeated starts for pre-cat exhaust gas dew points, cylinder bank 2 |
FWMKATW |
Factor for heat quantities during repeated starts for dew points after main catalyst |
FWMKATW2 |
Factor for heat quantities during repeated starts for dew points after main catalyst, cylinder bank 2 |
IMTUMTAT |
Integration threshold air mass for determining ambient temperature from TANS |
KATMEXML |
Exothermic reaction temperature in catalyst, tkatm |
KATMEXML2 |
Exothermic reaction temperature in catalyst, cylinder bank 2 |
KATMIEXML |
Exothermic reaction temperature in catalyst, tikatm |
KATMIEXML2 |
Exothermic reaction temperature in catalyst, tikatm, cylinder bank 2 |
KFATLAK |
Map for lambda correction for manifold exhaust gas temperature |
KFATLAK2 |
Map for lambda correction for manifold exhaust gas temperature, cylinder bank 2 |
KFATMABKA |
Factor for exhaust gas temperature decrease as a function of stop time and ambient temperature |
KFATMABKA2 |
Factor for exhaust gas temperature decrease as a function of stop time and ambient temperature, cylinder bank 2 |
KFATMABKK |
Factor for reducing the catalyst temperature as a function of stop time and ambient temperature |
KFATMABKK2 |
Factor for reducing the catalyst temperature as a function of stop time and ambient temperature, cylinder bank 2 |
KFATMKR |
Map for steady-state manifold exhaust gas temperature as a function of engine speed and relative cylinder charge |
KFATMKR2 |
Map for steady-state manifold exhaust gas temperature, cylinder bank 2 |
KFATMLA |
Map for exhaust gas temperature correction as a function of lambda |
KFATMLA2 |
Map for exhaust gas temperature correction as a function of lambda, cylinder bank 2 |
KFATMZW |
Map for exhaust gas temperature correction as a function of igntion angle correction |
KFATMZW2 |
Map for exhaust gas temperature correction as a function of ignition angle, cylinder bank 2 |
KFATZWK |
Map for ignition angle correction for manifold gas temperature |
KFATZWK2 |
Map for ignition angle correction for manifold gas temperature, cylinder bank 2 |
KFTATM |
Map for exhaust gas temperature as a function of engine speed and relative cylinder charge |
KFTATM2 |
Map for exhaust gas temperature as a function of engine speed and relative cylinder charge for cylinder bank 2 |
KFWMABG |
Map for heat quantity threshold exhaust gas dew points |
KFWMABG2 |
Map for heat quantity threshold exhaust gas dew points, cylinder bank 2 |
KFWMKAT |
Map for heat quantity threshold dew points after catalyst |
KFWMKAT2 |
Map for heat quantity threshold dew points after catalyst, cylinder bank 2 |
KLATMILAE |
Exothermic temperature decrease through enrichment, tikatm |
KLATMILAE2 |
Exothermic temperature decrease through enrichment, tikatm, Bank 2 |
KLATMIZWE |
Exothermic temperature decrease in catalyst at later ignition angles, tikatm |
KLATMIZWE2 |
Exothermic temperature decrease in catalyst at later ignition angles, tikatm, Bank 2 |
KLATMLAE |
Exothermic temperature decrease through enrichment |
KLATMLAE2 |
Exothermic temperature decrease through enrichment, cylinder bank 2 |
KLATMZWE |
Exothermic temperature decrease in catalyst at later ignition angles, tkatm |
KLATMZWE2 |
Exothermic temperature decrease in catalyst at later ignition angles, cylinder bank 2 |
NTUMTAT |
Speed threshold for determining ambient temperature from TANS |
SEZ06TMUB |
Sample point distribution, ignition angle efficiency |
SLX06TMUW |
Sample point distribution, desired lambda |
SLY06TMUW |
Sample point distribution, desired lambda, cylinder bank 2 |
SML06TMUW |
Sample point distribution, air mass, 6 sample points |
SML07TMUW |
Sample point distribution, air mass, 7 sample points |
SMT06TMUW |
Sample point distribution, air mass, 6 sample points |
ST107TMUB |
Sample point distribution, start temperature at front probe |
ST207TMUB |
Sample point distribution, start temperature at front probe, cylinder bank 2 |
ST307TMUB |
Sample point distribution, start temperature at rear probe |
ST407TMUB |
Sample point distribution, start temperature at rear probe, cylinder bank 2 |
STM05TMUB |
Sample point distribution, engine start temperature |
STS06TMUW |
Sample point distribution, exhaust gas mass flow |
STU05TMUB |
Sample point distribution, simulated ambient temperature |
SY_STERVK |
System constant condition: stereo before catalyst |
SY_TURBO |
System constant: turbocharger |
TABGMEX |
Exhaust gas temperature below the catalyst switch-off temperature |
TASTBFA |
Model temperature before pre-cat initial value via B_faatm requirement |
TATMKH |
Exhaust gas temperature correction via catalyst heating active |
TATMKH2 |
Exhaust gas temperature correction via catalyst heating active, cylinder bank 2 |
TATMKRSA |
Exhaust gas temperature correction in manifold via boost switch-off |
TATMKW |
Exhaust gas temperature correction with catalyst warming active |
TATMSA |
Exhaust gas temperature correction via boost cut-off |
TATMSAE |
Exothermic temperature increase in boost |
TATMSAE2 |
Exothermic temperature increase in boost, cylinder bank 2 |
TATMSTI |
Initial value for tabgm, tkatm intial value through power fail |
TATMTMOT |
Engine temperature warmer Motor, for temperature correction during cold start conditions |
TATMTP |
Exhaust gas dew point temperature |
TATMTRKH |
Exhaust gas temperature correction via thermal reaction catalyst heating |
TATMTRKH2 |
Exhaust gas temperature correction via thermal reaction catalyst heating, cylinder bank 2 |
TATMWMK |
Temperature offset for calculating heat quantities |
TIKATMOE |
Temperature correction in catalyst without exothermic reaction, tikatm |
TKATMOE |
Temperature correction near catalyst without exothermic reaction, tkatm |
TKSTBFA |
Model temperature post-cat initial value via B_faatm requirement |
TNLATM |
Minimum ECU delay time for exhaust gas temperature model – Abstellzeit |
TNLATMTM |
When tmot > threshold ECU delay requirement B_nlatm = 1 |
TNLATMTU |
When tumg (tatu – ATM) > threshold ECU delay requirement |
TUMTAIT |
Initialising value for ambient temperature from TANS |
VTUMTAT |
Vehicle speed threshold for TANS ® ambient temperature |
WMABGKH |
Factor for heat quantity correction via catalyst heating for dew points |
WMABGKH2 |
Factor for heat quantity correction via catalyst heating for dew points, cylinder bank 2 |
WMKATKH |
Factor for heat quantity correction via catalyst heating for dew points after catalyst |
WMKATKH2 |
Factor for heat quantity correction via catalyst heating for dew points after catalyst, cylinder bank 2 |
ZATAKRML |
Time constant for exhaust gas temperature model (manifold) |
ZATAKRML2 |
Time constant for exhaust gas temperature model (manifold), cylinder bank 2 |
ZATMAML |
Time constant for exhaust gas temperature model |
ZATMAML2 |
Time constant for exhaust gas temperature model, cylinder bank 2 |
ZATMIKKML |
Time constant for catalyst temperature model – Temperature in catalyst tikatm during cooling |
ZATMIKKML2 |
Time constant for catalyst temperature model – Temperature in catalyst tikatm during cooling, bank 2 |
ZATMIKML |
Time constant for catalyst temperature model – Temperature in catalyst, tikatm |
ZATMIKML2 |
Time constant for catalyst temperature model – Temperature in catalyst, cylinder bank 2 |
ZATMKKML |
Time constant for catalyst temperature model – catalyst temperature tkatm during cooling |
ZATMKKML2 |
Time constant for catalyst temperature model – catalyst temperature tkatm during cooling, bank 2 |
ZATMKML |
Time constant for catalyst temperature model – catalyst temperature tkatm |
ZATMKML2 |
Time constant for catalyst temperature model – catalyst temperature, cylinder bank 2 |
ZATMRML |
Time constant for exhaust gas temperature model – exhaust pipe wall temperature |
ZATMRML2 |
Time constant for exhaust gas temperature model – exhaust pipe wall temperature Bank 2 |
ZATRKRML |
Time constant for exhaust gas temperature model – manifold wall temperature |
ZATRKRML2 |
Time constant for exhaust gas temperature model – manifold wall temperature, cylinder bank 2 |
Variable |
Description |
B_ATMLL |
Condition for time constant during cooling at idle |
B_ATMLL2 |
Condition for time constant during cooling at idle |
B_ATMST |
Condition for tabgmst, tkatmst initial value calculation |
B_ATMST2 |
Condition for tabgmst, tkatmst calculation, cylinder bank 2 |
B_ATMTPA |
Condition: dew point before catalyst exceeded |
B_ATMTPA2 |
Condition: dew point 2 before catalyst exceeded |
B_ATMTPF |
Condition: dew point before catalyst exceeded (last trip) |
B_ATMTPF2 |
Condition: dew point before catalyst exceeded (last trip) cylinder bank 2 |
B_ATMTPK |
Condition: dew point after catalyst exceeded |
B_ATMTPK2 |
Condition: dew point 2 after catalyst exceeded |
B_ATMTPL |
Condition: dew point after catalyst exceeded (last trip) |
B_ATMTPL2 |
Condition: dew point after catalyst exceeded (last trip) cylinder bank 2 |
B_FAATM |
Condition: functional requirements for dew point end times |
B_KH |
Condition: catalyst heating |
B_KW |
Condition: catalyst warming |
B_LL |
Condition: idle |
B_NACHL |
Condition: ECU delay |
B_NACHLEND |
Condition: ECU delay ended |
B_NLATM |
Condition: ECU delay exhaust gas temperature model probe protection |
B_PWF |
Condition: Power fail |
B_SA |
Condition: Overrun cut-off |
B_ST |
Condition: Start |
B_STEND |
Condition: End of start conditions achieved |
B_STNDNL |
Condition: Beginning of ECU delay or end of start conditions (1 ® 0) |
B_TFU |
Condition: Ambient temperature sensor available |
B_TRKH |
Condition: Catalyst heating, thermal reaction effective |
B_UHRRMIN |
Condition: timer with a relative number of minutes |
B_UHRRSEC |
Condition: timer with a relative number of minutes |
DFP_TA |
ECU internal error path number: intake air temperature TANS (charge air) |
DFP_TUM |
ECU Internal error path number: ambient temperature |
ETAZWIMT |
Actual ignition angle efficiency average for exhaust gas temperature model (200 ms) |
ETAZWIST |
Actual ignition angle efficiency |
E_TA |
Error flag: TANS |
E_TUM |
Error flag: ambient temperature tumg |
IMLATM |
Integral of air mass flows from engine start bis Max.wert |
IMLATM_W |
Integral of air mass flows from end of start conditions up to the maximum value, (Word) |
IWMATM2_W |
Heat quantity for Condensation - dew points exhaust gas/catalyst (word), cylinder bank 2 |
IWMATM_W |
Heat quantity for Condensation - dew points exhaust gas/catalyst (word) |
LAMSBG2_W |
Desired lambda limit (word), cylinder bank 2 |
LAMSBG_W |
Desired lambda limit (word) |
ML_W |
Filtered air mass flow (word) |
NMOT |
Engine speed |
RL |
Relative cylinder charge |
TABGKRM2_W |
Exhaust gas temperature in manifold from the model, cylinder bank 2 |
TABGKRM_W |
Exhaust gas temperature in manifold from the model |
TABGM |
Exhaust gas temperature before catalyst from the model |
TABGM2 |
Exhaust gas temperature before catalyst from the model, cylinder bank 2 |
TABGM2_W |
Exhaust gas temperature before catalyst from the model (word) cylinder bank 2 |
TABGMAB |
Exhaust gas temperature during engine switch-off |
TABGMAB2 |
Exhaust gas temperature during engine switch-off (model) cylinder bank 2 |
TABGMST |
Exhaust gas temperature at engine start |
TABGMST2 |
Exhaust gas temperature at engine start, cylinder bank 2 |
TABGM_W |
Exhaust gas temperature before catalyst from the model (word) |
TABSTATM_W |
Stop time in ECU delay for exhaust gas temperature model |
TABSTMX_W |
Stop time maximum query for exhaust gas temperature model |
TABST_W |
Stop time |
TAKRKF |
Steady-state manifold exhaust gas temperature without correction |
TAKRKF2 |
Steady-state manifold exhaust gas temperature without correction, cylinder bank 2 |
TAKRSTC |
Steady-state exhaust gas temperature in manifold in °C |
TAKRSTC2 |
Steady-state exhaust gas temperature in manifold, cylinder bank 2 |
TANS |
Intake air temperature |
TATAKRML |
Output from PT1 element: exhaust gas temperature influence on tabgkrm |
TATAKRML2 |
Output from PT1 element: exhaust gas temperature influence on tabgkrm, cylinder bank 2 |
TATMAML |
Output from PT1 element: exhaust gas temperature influence on tabgm |
TATMAML2 |
Output from PT1 element: exhaust gas temperature influence on tabgm, cylinder bank 2 |
TATMKF |
Exhaust gas temperature before catalyst from map KFTATM |
TATMKF2 |
Exhaust gas temperature before catalyst from map KFTATM, cylinder bank 2 |
TATMRML |
Output from PT1 element: exhaust pipe wall temperature effect from tabgm |
TATMRML2 |
Output from PT1 element: exhaust pipe wall temperature effect from tabgm, cylinder bank 2 |
TATMSTA |
Exhaust gas temperature before catalyst from the steady-state model |
TATMSTA2 |
Exhaust gas temperature before catalyst from the steady-state model, cylinder bank 2 |
TATRKRML |
Output from PT1 element: exhaust pipe wall temperature effect from tabgkrm |
TATRKRML2 |
Output from PT1 element: exhaust pipe wall temperature effect from tabgkrm, cylinder bank 2 |
TATU |
Intake air temperature or ambient temperature |
TEXOIKM2_W |
Exotherme temperature increase in catalyst for tikatm, cylinder bank 2 |
TEXOIKM_W |
Exotherme temperature increase in catalyst for tikatm |
TEXOM2_W |
Exotherme temperature increase in catalyst for tkatm2, cylinder bank 2 |
TEXOM_W |
Exotherme temperature increase in catalyst for tkatm |
TIKATM |
Exhaust gas temperature in catalyst from the model |
TIKATM2 |
Exhaust gas temperature in catalyst from the model, cylinder bank 2 |
TIKATM2_W |
Exhaust gas temperature in catalyst from the model, cylinder bank 2 |
TIKATM W |
Exhaust gas temperature in catalyst from the model |
TKATM |
Catalyst temperature from the model |
TKATM2 |
Catalyst temperature from the model, cylinder bank 2 |
TKATM2_W |
Catalyst temperature from the model (word), cylinder bank 2 |
TKATMAB |
Exhaust gas temperature after catalyst through engine switch-off (model) |
TKATMAB2 |
Exhaust gas temperature after catalyst through engine switch-off (model), cylinder bank 2 |
TKATMST |
Catalyst temperature model initial value as a function of switch-off value, switch-off time |
TKATMST2 |
Catalyst temperature model initial value as a function of switch-off value, switch-off time, bank 2 |
TKATM_W |
Catalyst temperature from the model (word) |
TMOT |
Engine temperature |
TMST |
Engine start temperature |
TUMG |
Ambient temperature |
VFZG |
Vehicle speed |
ZWMATM |
Counter for repeated starts and factor for heat quantity threshold |
ZWMATM2 |
Counter for repeated starts and factor for heat quantity threshold, cylinder bank 2 |
ZWMATMF |
Counter for repeated starts and factor for heat quantity threshold upstream |
ZWMATMF2 |
Counter for repeated starts and factor for heat quantity threshold upstream, cylinder bank 2 |